Evaluasi Sistem Pencahayaan dan Penggunaan Energi Listrik pada Lampu Sorot di Gelanggang Olah Raga Kridosono Yogyakarta

Agityawan Ranga Manyurang, Bambang Sudibya

Submitted : 2021-11-29, Published : 2022-01-19.

Abstract

Kridosono Yogyakarta sports building is one of the sports facilities in the Kotabaru Yogyakarta. As the function of the exercise routine for this sports building is basketball and volleyball, the use at night of course uses an artificial lighting system. Artificial lighting, especially spotlights that have been installed based on information from the sports building manager, is still lacking in the sense of lack of light. For this reason, this study aims to evaluate the lighting system and calculate the use of floodlight electrical energy after and before the evaluation. The results showed that the average lighting level in the Kridosono Sports Building Yogyakarta did not meet the minimum standard of 200 Lux. Recommendations through the calculation of lighting levels obtained results of 211.2 lux and 202.75 lux. For the DIALux 4.13 simulation using a Philips BVP130 1xLED210/740 spotlight and a Philips BVP130 1 xLED172/830 spotlight, the results are 240 lux and 230 lux. The total electrical energy consumption of the floodlights before the evaluation was 752 kWh/month and after being re-planned by replacing the spotlights using Philips BVP130 1xLED172/830 of 678.3 kWh/month so as to save electrical energy by 9.8% and using Philips BVP130 spotlights 1xLED210/740 electricity consumption is 670kWh/month so that it saves electrical energy by 10.9%.

Keywords

Lighting System, Electrical Energy, DIALux 4.13

Full Text:

PDF

References

Hutauruk, Fajar Okasantoso., Atmam, dan Situmeang, Usaha. (2017) Analisis Intensitas Pencahayaan Pada Lapangan Planet Futsal Rumbai Pekanbaru. Jurnal Sain, Energi, Teknologi & Industri, 2(1), 1-10.

Badan Standar Nasional (BSN). (2000). SNI 03-6197-2000: Konservasi Energi Sistem Pencahayaan pada Bangunan Gedung. Jakarta: Badan Standarisasi Nasional.

Madarina, Najma., Asmoro, Wiratno A., dan Justiono, Heri. (2013). “Perancangan Pencahayaan GOR ‘Target’ Keputih dengan Menganalisa Daya serta Menerapkan Konsep Green Building. Jurnal Teknik Pomits, 2(2), 150-155.

Edison, Kentiler., Situmeang, Usaha., dan Monice. (2019). Analisis Sistem Pencahayan Terhadap Pemakaian Daya di Perpustakaan Universitas Lancang Kuning. Teknologi dan Sains, 5(1), 1-7.

Isnaeni, Lailatul., Santoso, Hari Hadi., dan Wati, Erna Kusuma. (2019). Optimasi Sistem Pencahayaan Gedung Olah raga Hoki di kota Administrasi Jakarta Selatan. Jurnal ilmiah GIGA, 22(1), 33-42.

Sumardjati P. (2008). Teknik Pemanfaatan Tenaga Listrik untuk Sekolah Menengah Kejuruan. Journal of Chemical Information and Modeling, 53, 1689–1699.

Muhaimin, M.T. (2001). Teknologi Pencahayaan. Bandung: PT. Refika Aditama.

Zakeri, Behnam., & Syri, Sanna. (2015). Electrical Energy Storage Systems: A Comparative Life Cycle Cost Analysis. Renewable and Sustainable Energy Reviews, Elsevier, 42(C), 569-596.

Philips Lighting. (1986). Light and Perception. Netherlands: Philips Lighting.

European Committee for Standardization. (2007). BS EN 12193:2007: Light and Lighting-Sports Lighting. London: European Committee for Standardization.

Wilhm, J.L. & T.C. Dorris. (1968). Biological Parameters for Water Quality Criteria. BioScience, 18(6), 477-481.

Article Metrics

Abstract view: 511 times
Download     : 618   times

Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 International License.

Refbacks

  • There are currently no refbacks.