Feasibility Test Based on Insulation, Ratio and Internal Protection for 20 MVA Power Transformer of 150/20 kV Substation

Fajar Bagus Ramadhan, Muhamad Haddin

Submitted : 2025-03-02, Published : 2025-05-14.

Abstract

The problems that occur in 20 MVA power transformers are insulation feasibility issues, voltage regulation and internal relay malfunctions. The impact is to cause a degradation of transformer reliability. The solution is how to ensure the feasibility of the transformer by evaluating the transformer feasibility test including the insulation subsystem, voltage ratio, and internal relay. This research discusses the feasibility of a 20 MVA transformer based on insulation, voltage ratio and internal relay. The model is a set of 20 MVA transformer GI 150 kV. The test method is carried out using polarization index, tangent delta, breakdown voltage, voltage ratio and sudden pressure relay function test. The references of all test methods are IEEE Std 62-1995 standard for polarization index, CIGRE TB 445 for tangent delta, IEC 60156-02-1995 for breakdown voltage, IEEE C57.125.1991 standard for voltage ratio and internal relay test validated using Proteus application. The test methods proved effective for evaluating the 20 MVA transformer feasibility test. This is evidenced by the worst value of 1.06 in testing the polarization index of the secondary to tertiary winding. Then 0.53% of tap voltage ratio 17 phase T and 0.58% of tap voltage ratio 18 phase T. The internal relay works as it should. The results obtained, the transformer is in an unfit condition and there needs to be further investigated so that it can be normally operated.

Keywords

Polarization index; tangent delta; breakdown voltage; ratio; internal relay.

Full Text:

PDF

References

R. F. Rifqyawan, “Analisis Kelayakan Tahanan Isolasi Trafo 30 MVA di GI 150/20 KV PT APF dengan Menggunakan Indeks Polarisasi dan Tangen Delta [Feasibility Analysis of 30 MVA Transformer Insulation Resistance at 150/20 kV Substation of PT APF Using Polarization Index and Tangent Delta],” Thesis, Department of Electrical Engineering, Universitas Islam Sultan Agung, 2023. (In Indonesian)

K. Ababil, “Analisa Perbandingan Kelayakan Tahanan Isolasi Transformator Daya Menggunakan Pengujian Indeks Polaritas, Tangen Delta, BDV (Breakdown Voltage), dan Rasio Tegangan di Gardu Induk 150 KV Ulee Kareng [Comparative Analysis of Power Transformer Insulation Resistance Feasibility Using Polarization Index, Tangent Delta, BDV, and Voltage Ratio Tests at 150 kV Ulee Kareng Substation],” Thesis, Department of Electrical Engineering, Universitas Islam Sultan Agung 2023. (In Indonesian)

M. F. Robbani et al., “Penentuan Kelayakan Tahanan Isolasi pada Transformator 60 MVA di Gardu Induk 150 kV Tegal dengan Menggunakan Indeks Polarisasi, Tangen Delta, dan Breakdown Voltage [Determining the Insulation Resistance Feasibility on a 60 MVA Transformer at 150 kV Tegal Substation Using Polarization Index, Tangent Delta, and Breakdown Voltage],” Elektrika, vol. 12, no. 2, pp. 60–66, 2020. https://doi.org/10.26623/elektrika.v12i2.2721 (In Indonesian)

C. Widyastuti and R. A. Wisnuaji, “Analisis Tegangan Tembus Minyak Transformator di PT. PLN (Persero) Bogor [Breakdown Voltage Analysis of Transformer Oil at PT. PLN (Persero) Bogor],” Elektron, vol. 11, pp. 75–78, 2019. (In Indonesian)

G. A. Prima, Z. Anthony, and A. Anugrah, “Analisa Tahanan Isolasi Pada Transformator Daya 150 / 30 kV Gardu Induk Padang Luar PT PLN (Persero) Bukittinggi [Analysis of Insulation Resistance on 150/30 kV Power Transformer at Padang Luar Substation PT PLN (Persero) Bukittinggi],” INAJET, vol. 6, no. 1, pp. 23–33, 2023. (In Indonesian)

PT. PLN (Persero), “Pedoman Pemeliharaan Peralatan Penyaluran Tenaga Listrik PT PLN (Persero) di Regional Jawa Madura Bali [Maintenance Guidelines for Power Transmission Equipment at PLN Java-Madura-Bali Region],” PT PLN (Persero) Regional Jamali Divisi RJT, 2022. (In Indonesian)

C. B. Waluyo, “Pengenalan simulasi elektronika dengan Software Proteus 8 Profesional [Introduction to Electronics Simulation with Proteus 8 Professional Software],” Calesmart. [Online]. Available: https://calesmart.com/artikel/Pengenalan-simulasi-elektronika-dengan-Software-Proteus-8-Profesional_132.html (In Indonesian)

A. P. Nugraha and M. Haddin, “Isolation Resistance Feasibility Test Analysis Based on Polarization Index and Delta Tangent in,” IJISET, vol. 10, no. 06, pp. 98–106, 2023.

Institute of Electrical and Electronics Engineers (IEEE), Guide for Diagnostic Field Testing of Electric Power Apparatus Part 1: Oil Filled Power Transformers, Regulators, and Reactors, IEEE Std 62-1995, New York: Institute of Electrical and Electronics Engineers (IEEE), approved 16 March 1995. https://doi.org/10.1109/IEEESTD.1995.122640

C. Rajotte et al., “Cigré Brochure 445 - Guide for Transformer Maintenance,” CIGRE Technical Brochure, February 2011, p. 23.

International Electrotechnical Commission (IEC), “Iec 60156,” 61010-1 © Iec:2001, vol. 3, p. 13, 2018.

IEEE Std C57.125-1991: IEEE Guide for Failure Investigation, Documentation, and Analysis for Power Transformers and Shunt Reactors, IEEE 2015, 2015. [Online]. Available: http://lib.ugent.be/catalog/ebk01:3780000000090758

G. Treff, K. Winkert, M. Sareban, J. M. Steinacker, and B. Sperlich, “The Polarization-Index: A Simple Calculation to Distinguish Polarized From Non-polarized Training Intensity Distributions,” Frontiers in Physiology, vol. 10, 2019. https://doi.org/10.3389/fphys.2019.00707

PT. PLN (Persero), “Pemeliharaan OLTC [OLTC Maintenance],” Jakarta: PT. PLN (Persero) Pusat Pendidikan dan Pelatihan, 2009. (In Indonesian)

A. Akbari, P. Werle, H. Borsi, and E. Gockenbach, “Transfer function-based partial discharge localization in power transformers: a feasibility study,” IEEE Electrical Insulation Magazine, vol. 18, no. 5, pp. 22–32, 2002. https://doi.org/10.1109/MEI.2002.1044318

V. Srividhya et al., “Determination of Breakdown Voltage for Transformer Oil Testing Using ANN,” in Congress on Intelligent Systems, H. Sharma, M. Saraswat, A. Yadav, J. H. Kim, and J. C. Bansal, Eds., Singapore: Springer Singapore, 2021, pp. 443–452. https://doi.org/10.1007/978-981-33-6981-8_35

A. Pramono, M. Haddin, and D. Nugroho, “Analisis Minyak Transformator Daya Berdasarkan Dissolved Gas Analysis (Dga) Menggunakan Data Mining Dengan Algoritma J48 [Analysis of Power Transformer Oil Based on Dissolved Gas Analysis Using Data Mining with J48 Algorithm],” Telematika, vol. 9, no. 2, p. 78, 2016. https://doi.org/10.35671/telematika.v9i2.457 (In Indonesian)

G. Ramesh, A. Sharma, and H. Thakkar, “The Impact of the Use of Dry Lubricating Compound on the Dielectric Properties of Solid and Liquid Insulation of a Power Transformer,” in 2022 7th International Advanced Research Workshop on Transformers (ARWtr), 2022, pp. 24–29. https://doi.org/10.23919/ARWtr54586.2022.9959946

O. Thiessaputra, M. Haddin, and S. A. D. Prasetyowati, “DGA Method Based on Fuzzy for Determination of Transformer Oil Quality,” Proceedings of International Conference on Smart Computing and Cyber Security, vol. 149, 2021. https://doi.org/10.1007/978-981-15-7990-5_11

J. H. Buchanan, “Design, construction, and testing, of voltage transformers,” Journal of the Institution of Electrical Engineers, vol. 78, no. 471, pp. 292–309, 1936. https://doi.org/10.1049/jiee-1.1936.0049

O. W. Iwanusiw and P. Eng, “The Art and Science of Transformer Ratio Measurement,” in 2018 IEEE Electrical Insulation Conference (EIC), 2018, pp. 390–394. https://doi.org/10.1109/EIC.2018.8481036

R. L. Bean and H. L. Cole, “A Sudden Gas Pressure Relay for Transformer Protection [includes discussion],” Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, vol. 72, no. 3, pp. 480–483, 1953. https://doi.org/10.1109/AIEEPAS.1953.4498657

K. T. Muthanna, A. Sarkar, K. Das, and K. Waldner, “Transformer insulation life assessment,” IEEE Transactions on Power Delivery, vol. 21, no. 1, pp. 150–156, 2006. https://doi.org/10.1109/TPWRD.2005.855474

S. HS, E. P. Sinulingga, H. P. Nugroho, and A. Nasution, “Diagnosis of Transformer Isolation Using Dielectric Dissipation Factor (Tan Delta) and Insulation Resistance: A Review Study,” in 2021 5th International Conference on Electrical, Telecommunication and Computer Engineering (ELTICOM), 2021, pp. 1–4. https://doi.org/10.1109/ELTICOM53303.2021.9590184

C. K. Chakrabarty, A. R. Avinash, and A. G. Ahmad Basri, “Development of high frequency Tan Delta measurement method for 132kV transmission underground cables,” in 2014 IEEE 2nd International Symposium on Telecommunication Technologies (ISTT), 2014, pp. 436–441. https://doi.org/10.1109/ISTT.2014.7238250

D. Martin and Z. D. Wang, “Statistical analysis of the AC breakdown voltages of ester based transformer oils,” IEEE Transactions on Dielectrics and Electrical Insulation, vol. 15, no. 4, pp. 1044–1050, 2008, https://doi.org/10.1109/TDEI.2008.4591226

A. S. A. Razzaq, M. F. M. Yousof, S. M. Al-Ameri, M. A. Talib, and A. J. Mshkil, “Interpretation of Inter-Turn Fault in Transformer Winding Using Turns Ratio Test and Frequency Response Analysis,” International Journal of Electrical and Electronic Engineering and Telecommunications, vol. 11, no. 3, pp. 218–225, 2022. https://doi.org/10.18178/ijeetc.11.3.218-225

A. Hukoro and M. Khosyi’in, “Sistem Monitoring Impressed Current Cathodic Protection Berbasis IoT untuk Lambung Kapal [IoT-Based Monitoring System for Impressed Current Cathodic Protection on Ship Hulls],” CYCLOTRON, vol. 8, no. 1, pp. 48–55, 2025. (In Indonesian)

M. N. Aravind and O. D. Naidu, “Parameter Estimation of Power Transformer in Presence of Bad Measurement Data,” in 2021 1st International Conference on Power Electronics and Energy (ICPEE), 2021, pp. 1–6. https://doi.org/10.1109/ICPEE50452.2021.9358765

Article Metrics

Abstract view: 176 times
Download     : 62   times

Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 International License.

Refbacks

  • There are currently no refbacks.